G5 Ex module 4 inputs/2 valve outputs |
General specifications | ||
---|---|---|
Node type | Standard node | |
EC-Type Examination Certificate | DMT 02 ATEX E 125 | |
Group, category, type of protection | II (1GD) 2G Ex e mb [ia] IIB/IIC T4 Intrinsically safe input and output circuits can be laid in the 1G and 1D category areas. |
|
Indicators/operating means | ||
LED PWR/CHK | dual LED green/red green: AS-Interface voltage red flashing: communication error or address 0 or SC/LK error |
|
LED IN | 4 dual LED yellow/red yellow: switching state (input) red flashing: SC/LK error |
|
LED OUT | Switching state (output); 2 LED yellow | |
Electrical specifications | ||
Rated operating voltage | 26.5 ... 31.6 V PELV from AS-Interface | |
Rated operating current | ≤ 90 mA | |
Maximum safe voltage | 40 V | |
Short-circuit current | ≤ 35 A | |
Input | ||
Number/Type | 4 inputs according to IEC 60947-5-6 (NAMUR, DIN 19234) | |
Switching point | OFF ≤ 1.2 mA ON ≥ 2.1 mA |
|
Values in accordance with EC-Type Examination Certificate | Extract; Other values for mixed and parallel circuits (2:1 mode): see EC-Type Examination Certificate | |
Voltage | ≤ 8.8 V DC | |
Current | ≤ 11.5 mA | |
Power | ≤ 25.3 mW | |
Internal resistor | ≥ 765 Ω | |
Internal capacitance | negligible | |
Internal inductance | negligible | |
Type of protection | ||
External capacitance | ||
External inductance | ||
L/R-ratio | ||
Characteristic curve | linear | |
Output | ||
Number/Type | 2 outputs for control of intrinsically safe valves | |
Values in accordance with EC-Type Examination Certificate | ||
Voltage | ≤ 28 V DC | |
Current | ≤ 110 mA | |
Power | ≤ 770 mW | |
Internal resistor | ≥ 258 Ω | |
Type of protection | ||
External capacitance | ||
External inductance | ||
L/R-ratio | ||
Characteristic curve | linear | |
Nominal values | (typically) | |
Open loop voltage | 26 V | |
Short-circuit current | 50 mA | |
Internal resistor | 270 Ω | |
Curve angle points (nominal values) | 12.5 V DC, 50 mA | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
AS-Interface | EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.F | |
IO code | 7 | |
ID code | F | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0/P1 | (Output conditions on failure of the AS-Interface communication or LB/LK error) 0/0 outputs unchanged 0/1 outputs not controllable 1/0 outputs controllable 1/1 outputs not controllable |
|
P2 | not used | |
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -20 ... 85 °C (-4 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP54 according to EN 60529 | |
Connection | screw terminals | |
Mass | 1.5 kg | |
Mounting | screw mounting | |
Tightening torque | Terminal compartment cover = 1.5 Nm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 130 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
AS-Interface | 48001 | ALL | 94 KB | |
Europe DMT ATEX Category (1) 2 | DMT 02 ATEX E 125 | ALL | 2158 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability
The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.